Digital Area Alarm

Pressure is monitored via a transducer in the pipeline downstream from the last AVSU, this pressure is monitored for both high and low pressure (low only for vacuum). A fault on the cabling between the pressure transducer and alarm panel would result in a system fault alarm and as a result, the integrity of the CPX cabling is incomparable.

CPX Digital Area Alarm is available in two different and versatile installation models. The alarm unit provides an indication of 3 conditions of gas, normal, Low pressure, and High pressure for up to 6 Gas services.

Each service has a green normal, red high-pressure, and red low-pressure indication, the vacuum service has a green normal and red low-pressure indication and is programmed via an antimicrobial touchscreen display.

Catalogue

Download Catalogue

Enter your Email

By clicking download you consent to Precision UK contacting you.

More Information
  • HTM 02-01 & SHTM02-01 fully compliant

  • Ultra Low 12V Digital Touchscreen Alarm

  • Anti-Microbial laminate label that actively removes bacteria

  • User configurable 1 to 6 gas types

  • Dual circuit pre-loaded gas identification enabling compliance to HTM02-01 criteria

  • Battery backup in case of power failure shall continue to operate for up to 24 hours

  • Modbus ASCI outputs for digital connection to BMS to monitor Live Local pressures within Hospital for all gas types

  • Integration to CPX ‘Hospi-View’ Schematic BMS system

  • Lockable Enclosure

Warranty

No parts or labor charges for repairs to alarms that fail due to faulty parts or manufacture. 10-year compatibility warranty: Install the CPX-DA with confidence that equipment will be available to modify or extend the system for at least 10 years.

All Alarms are manufactured under our strict BS EN 13485 Medical Devices: Quality Management Systems.

Product Codes

Product Code

Model
CPX-DA-REM-FB Digital Alarm – Remote Type
CPX-DA-FB CPX Digital Alarm – Flush Box Type